SA-K5 sounder

SA-K5 SOUNDER FOR FIRE ALARM SYSTEMS HOLDS DOCUMENTS ISSUED BY THE CNBOP-PIB:

  • CPR CERTIFICATE NO. 1438-CPR-0010
  • CERTIFICATE OF APPROVAL NO. 5301/2024

ATTENTION! Documents to be downloaded after logging in to the Client Zone

Use:

This sounder is destined for acoustic signalling in indoor fire alarm systems and for other uses in accordance with the following signal possibilities, e.g. a ISO 8201 to alarm about a wrong condition of a machine. The SA-K5 alarm device is intended for indoor applications.


Construction:

The SA-K5 sounder consists of two parts, the first of which is the right alarm device in a housing of non-combustible material. It contains a supply voltage terminal and pins which allow you to select the type of sound. The alarm device has a choice of four acoustic signals. A piezoceramic transducer was used as the source of sound. With the use of the WSD-1 audible signal switch it is possible to switch off an audible signal. The second part – a socket is a mounting element which fixes the alarm device to the ceiling or wall by PIP-1AN cable junction box or by means of two screws and anchor pegs.


Opening:

To open the alarm device you should: twist the shade to the left while holding the base. After that move apart the shade and the base.

Closing:

To close the alarm device you should adjust the markers. After that assemble the device and twist it to the direction marked with an arrow (sequence shown in the drawing).

SA-K5 closing scheme

Type sounder
Supply voltage 16 – 32,5 V DC
Current consumption in off state 0 mA
Current consumption in on state <50 mA*
Power consumption in on state <1,2 W*
Sound output >100 dB*
Flash frequency not applicable
Flash time not applicable
Time between flashes not applicable
Device category not applicable
Device type type A
Working temperature -10°C ÷ +55°C
IP protection degree IP33
IK protection degree not applicable
Conductor cross-section 2,5 mm2
Dimensions Ø 115×62 mm
Weight ~181 g

*for Uz=24 V DC, fire service signal

SA-K5 connection diagram:

 

Jumper settings:

A – Ambulance siren tone
P – Police siren tone
S – Fire brigade siren tone
M – ISO 8201

Notice: SA-K5 alarm device should be mounted by PIP-1AN cable junction box.

Cooperating products

osłona zabezpieczająca OZ-40

OZ-40-2 cover

Use: The OZ-40-2 cover is destined to protect W2 signalling devices as well as fire detectors or other devices which…

OM-1 mounting sleeve

Use: Mounting Sleeves OM-1 are used to mount the signalling devices manufactured by the W2 company in suspended ceilings, coffered…

wyłącznik akustyczny pożarowego sygnału dźwiękowego

WSD-1 audible signal switch

Use: The WSD-1 audible signal switch is destined for collaboration with: sounders type SA-K5, SA-K6, SA-K7 sounders type SA-P8, sounders…

PIP-1AN cable distribution junction box

PIP-1AN cable distribution junction box

PIP-1AN CABLE DISTRIBUTION JUNCTION BOX HOLDS DOCUMENTS ISSUED BY CNBOP-PIB: THE NATIONAL CERTIFICATE OF CONSTANCY OF PERFORMANCE NO. 063-UWB-0194 NATIONAL…