SG-Pgw3 voice sounder

VOICE SOUNDER SG-Pgw3 HOLDS DOCUMENTS ISSUED BY CNBOP-PIB:

  • CERTIFICATE CPR NO. 1438-CPR-0746
  • CERTIFICATE OF APPROVAL NO. 4234/2021

ATTENTION! Documents to be downloaded after logging in to the Client Zone

Use:

Signalling device with voice messages is intended for signalling a fire alternately with acoustic signal and voice message signal. Voice sounder SG-Pgw3 is intended for indoor applications.


Construction:

The signalling device has a plastic casing that contains electronic components. The casing consists of three parts: a body with a speaker installed, a cover with a printed circuit, and a base that can be mounted on a wall / a ceiling or directly to a PIP-3AN box.
Cover contains:

  • power supply connection,
  • connection for a  WSD-1 switch,
  • micro USB connection,
  • potentiometer for volume adjustment,

The power supply connection has three terminals marked as “+1”, “+2”, “GND”. The USB connection makes it possible to copy messages from a PC to the internal memory of the device.  The signalling device can emit up to 18 patterns of acoustic signals; it is also possible to choose the “no acoustic signal” option.


Cooperation with WSD-1 audible signal switch:

When the signalling device has to be deactivated locally, the user can use the attested sound signal switch WSD-1. The signalling device has a connection block for connecting the switch. On connecting the WSD-1 switch, pressing the key deactivates the sound signal of the device. The condition is active as long as voltage is present on the terminals of the device. The active condition of the switched is indicated with the LED on the switch key.

Attention!

The WSD-1 switch is powered directly from the sounder (it does not require external power supply).


Opening:

To open the signalling device: screw out the screw locking the base, turn the shade anticlockwise while holding the base, then separate the shade and the base.

Closing:

To close the signalling device: fit together the markers. After that put together the device and turn in the direction marked with an arrow (the sequence in the drawing). On closing, lock the base by screwing in the locking screw.


Installation recomendation:

SG-Pgw3 signalling devices should be connected to Fire Alarming System by means of junction boxes featuring fire resistance (PIP-3AN is recommended). The junction box should be mounted to a ceilling / wall, which should also have required fire resistance. In the case when for an esthetic reasons installation of signalling device directly on PIP-3AN junction box is impossible, it is admissible to install a signalling device on substrate that does not have required fire resistance, however the junction box must be mounted on substrate having required fire resistance (e.g. a situation, in which a PIP-3AN junction box is mounted to a ceiling having E90 fire resistance, while the SG-Pgw3 signalling device is mounted on a suspended ceiling).

Type voice sounder
Supply voltage 20-32,5 V DC
Current consumption in off state 0 mA
Current consumption in on state <220 mA*
Power consumption in on state <5,28 W*
Sound output >90 dB*
Flash frequency not applicable
Flash time not applicable
Time between flashes not applicable
Device category not applicable
Device type type A
Working temperature -10°C ÷ +55°C
IP protection degree IP31C
IK protection degree not applicable
Conductor cross-section 2,5 mm²
Dimensions Ø 115×78 mm
Weight ~325 g

*for Uz=24 V DC, fire alarm, potentiometer maximum

Control:

Connecting the supply voltage to appropriate terminals triggers the generation of the alarm sequence in accordance with the programmed function.

Attention!

Providing the supply voltage to: input +1 will play the message K1.mp3, input +2 will play the message K2.mp3, inputs +1 and +2 will play the message K3.mp3.


Control – devices network

SG-Pgw2 voice sounder can be used to build networks of synchronously operating signalling devices. Signalling devices in the network do not require addressing – no need to programme signalling devices in the master/slave mode. There is also the option to automatically copy messages to all the signalling devices present in the network – a feature which is useful for updating message content.

Attention!

For proper operation of the bus, 120 Ω resistors must be applied at the ends of the bus.
The maximum number of signalling devices operated in one network is 10.
The maximum length of the bus should not exceed 200 m


Announcements:

Announcement 1:
Uwaga! Uwaga! W budynku wykryto pożar, proszę zastosować się do instrukcji przeciwpożarowej.
Attention! Attention! Fire in the building, please follow fire safety instructions immediately.
Achtung! Achtung! Im Gebäude wurde Brand entdeckt, richten Sie sich bitte nach den Brandschutzmaßnahmen.

Announcement
2:
Uwaga! Uwaga! Zagrożenie zostało zlikwidowane, odwołuje się alarm ewakuacyjny.
Attention! Attention! The fire risk has been eliminated, fire alarm has been cancelled.
Achtung! Achtung! Die Brandgefahr wurde beseitigt, der Evakuierungsalarm wird abgesagt.

Announcement 3:
Uwaga! Uwaga! Z powodu zagrożenia pożarowego budynku, zaistniała potrzeba ewakuacji. Proszę o niezwłoczne opuszczenia budynku, najkrótszą z możliwych dróg.
Attention! Attention! There is fire risk in the building, evacuation is required. Please leave the building immediately by the shortest possible route.
Achtung! Achtung! Im Gebäude wurde Feuergefahr gemeldet und das Gebäude muss Evakuiert werden. Bitte verlassen Sie sofort das Gebäude über den nächstgelegenen Ausgang.


Programming:

It is recommended to use the USB cable for alarm devices.

To work properly, the signaling device requires a configuration file and * .mp3 files with the content of messages. In order to copy files with recordings, disconnect the supply voltage from the device terminals. Then connect the device to the USB port of the PC / laptop with a USB A / micro USB cable (data transmission function required). After connecting the cable, the siren will be visible in the operating system as a mass storage device. Then, copy the files with sound recordings to the siren.

The user should remember to keep the nomenclature of file names with names recognized by the signaling device, i.e. the first message “K1.mp3”, the second message “K2.mp3”, etc.

The next step is to modify the configuration file. In this file, the user selects the siren number as well as the auto-update option. User can choose 1 of 18 siren patterns or no siren.

In case of loss of the configuration file, the file is available for download at www.w2.com.pl after logging in to the MY ACCOUNT.

Cooperating products

USB cable for alarm devices

Use: USB type A – microUSB type B cable designed for alarm devices: SG-Pgw3 SGO-Pgw SGO-Pgz3 SG-Wgw2 SG-Wgw2 IP65 Cable…

osłona zabezpieczająca OZ-40

OZ-40-2 cover

Use: The OZ-40-2 cover is destined to protect W2 signalling devices as well as fire detectors or other devices which…

OM-1 mounting sleeve

Use: Mounting Sleeves OM-1 are used to mount the signalling devices manufactured by the W2 company in suspended ceilings, coffered…

wyłącznik akustyczny pożarowego sygnału dźwiękowego

WSD-1 audible signal switch

Use: The WSD-1 audible signal switch is destined for collaboration with: sounders type SA-K5, SA-K6, SA-K7 sounders type SA-P8, sounders…

puszka instalacyjna PIP-1AN

PIP-3AN cable distribution junction box

PIP-3AN CABLE DISTRIBUTION JUNCTION BOX HOLDS DOCUMENTS ISSUED BY CNBOP-PIB: NATIONAL CERTIFICATE OF CONSTANCY OF PERFORMANCE NO. 063-UWB-0194 NATIONAL TECHNICAL…