SGO-Pgz3 outdoor voice sounder with visual alarm device

SGO-Pgz3 OUTDOOR VOICE SOUNDER WITH VISUAL ALARM DEVICE HOLDS DOCUMENTS ISSUED BY CNBOP-PIB:

  • CERTIFICATE CPR NO. 1438-CPR-0823

ATTENTION! Documents to be downloaded after logging in to the Client Zone

Use:

SGO-Pgz3 signalling device with voice messages is intended for signalling a fire alternately with acoustic signal and voice message signal. Additionally, the signaling device generates a flash optical signal. SGO-Pgz3 voice sounder with VAD is intended for outdoor applications.


Construction:

The signaling device has a housing made of non-flammable material with electronic components inside. The housing consists of three parts: a body with a mounted loudspeaker and electronic system, a lampshade covering the light source and a cover with holes enabling the emission of sound from the loudspeaker inside. Under the cover there are: a power supply connection, a connection for a  WSD-1 switch, a synchronisation line connection, a micro USB connection and a potentiometer for volume adjustment. The power supply connection has three terminals marked as “+1”, “+2”, “GND”. Connection of voltage in the appropriate range to the siren inputs enables playback of messages according to the table above. The USB connection makes it possible to copy messages from a PC to the internal memory of the device. The signalling device can emit up to 18 patterns of acoustic signals; it is also possible to choose the “no acoustic signal” option. A brand new signalling device has three messages downloaded to the memory and a fire siren set.


Cooperation with WSD-1 audible signal switch:

When the signalling device has to be deactivated locally, the user can use the sound signal switch WSD-1. The signalling device has a connection block for connecting the switch. On connecting the WSD-1 switch, pressing the key deactivates the sound signal of the device leaving optical part. The condition is active as long as voltage is present on the terminals of the device. The active condition of the switch is indicated with the LED on the switch key.

PLEASE NOTE!

Switch WSD-1 is supplied directly from the connection block of the signalling device. Do not connect external power supply to terminals of the WSD-1 block.


Varieties:

The SGO-Pgz3 sounder with VAD is available in 3 varieties, which differ in the arrangement of the optical color of the flash generated.

Varieties Description
SGO-Pgz3 outdoor voice sounder with VAD generating red light, lamp shade in RED
SGO-Pgz3/śb outdoor voice sounder with VAD generating white light, lamp shade in WHITE
SGO-Pgz3/śbcz outdoor voice sounder with VAD generating alternating red and white light, lamp shade in WHITE

Attention!

The PIP-3AN / 1.25A box is recommended for all types of SGO-Pgz3 signaling devices!


Opening:

In order to open the device: unscrew the screws securing the cover to the body and remove the cover.

Closing:

In order to close the device, place the cover on the siren body and tighten the fastening screws.

 

Type voice sounder with visual alarm device
Supply voltage 20-32,5 V DC
Current consumption in off state 0 mA
Current consumption in on state <1100 mA*
Power consumption in on state <26,4 W*
Sound output >100 dB**
Flash frequency ~0,5 Hz
Flash time ~190 ms
Time between flashes ~1800 ms
Device category O
Device type type B
Working temperature -25°C ÷ +70°C
IP protection degree IP33C
IK protection degree not applicable
Conductor cross-section 1,5 mm²
Dimensions 312 x 295 x 95 mm
Weight ~1402 g

*for Uz=24 V DC, Po=20Wrms, f=1 kHz

Attention!

The PIP-3AN / 1.25A box is recommended for all types of SGO-Pgz3 signaling devices!

Control:

Connecting the supply voltage to the terminals triggers the generation of the appropriate alarm and the output signal.

Attention!

Providing the supply voltage to: input +1 will play the message K1.mp3, input +2 will play the message K2.mp3, inputs +1 and +2 will play the message K3.mp3.


Control – devices network

If it is necessary to build a synchronously operating signaling network, all the “SA” lines of signaling devices included in one network and the “SB” lines should be interconnected

The 2-wire CAN bus standard was used as the communication interface. The “SA” line corresponds to the CAN H line, while the “SB” line corresponds to the CAN L line. After connecting the supply voltage to the terminals of all signaling devices, they start to work synchronously (light and sound). When a signaling device appears in the network with the value “auto-update” set to 1, the memory content of that signaling device will be copied to the other signaling devices in the network. The duration of the memory copying process depends on the number and length of recordings. For example, it takes about 10 minutes to copy files with a total size of 1.95 MB. After copying the memory contents, the network of devices will start if the copying process was successful. The occurrence of errors during the copying process will be signaled by short flashes of the signal lamp from which the memory contents were copied and the signal lamp with the error. During copying, the signaling devices emit short, quiet acoustic pulses.

PLEASE NOTE!

For the bus to work properly, it is required to use 120Ω resistors at the ends of the bus.Within one network there can be no more than 10 signaling devices. The length of the synchronization line should not exceed 400 m (tested with a cable type YnTKSYekw, 150nF / km, 0.7mH / km, 75Ω / km).


Announcements:

Announcement 1:
Uwaga! Uwaga! W budynku wykryto pożar, proszę zastosować się do instrukcji przeciwpożarowej.
Attention! Attention! Fire in the building, please follow fire safety instructions immediately.
Achtung! Achtung! Im Gebäude wurde Brand entdeckt, richten Sie sich bitte nach den Brandschutzmaßnahmen.

Announcement 2:
Uwaga! Uwaga! Zagrożenie zostało zlikwidowane, odwołuje się alarm ewakuacyjny.
Attention! Attention! The fire risk has been eliminated, fire alarm has been cancelled.
Achtung! Achtung! Die Brandgefahr wurde beseitigt, der Evakuierungsalarm wird abgesagt.

Announcement 3:
Uwaga! Uwaga! Z powodu zagrożenia pożarowego budynku, zaistniała potrzeba ewakuacji. Proszę o niezwłoczne opuszczenie budynku, najkrótszą z możliwych dróg.
Attention! Attention! There is fire risk in the building, evacuation is required. Please leave the building immediately by the shortest possible route.
Achtung! Achtung! Im Gebäude wurde Feuergefahr gemeldet und das Gebäude muss Evakuiert werden. Bitte verlassen Sie sofort das Gebäude über den nächstgelegenen Ausgang.


Programming:

It is recommended to use the USB cable for alarm devices.

To work properly, the signaling device requires a configuration file and * .mp3 files with the content of messages. In order to copy files with recordings, disconnect the supply voltage from the device terminals. Then connect the device to the USB port of the PC / laptop with a USB A / micro USB cable (data transmission function required). After connecting the cable, the siren will be visible in the operating system as a mass storage device. Then, copy the files with sound recordings to the siren.

The user should remember to keep the nomenclature of file names with names recognized by the signaling device, i.e. the first message “K1.mp3”, the second message “K2.mp3”, etc.

The next step is to modify the configuration file. In this file, the user selects the siren number as well as the auto-update option. User can choose 1 of 18 siren patterns or no siren.

In case of loss of the configuration file, the file is available for download at www.w2.com.pl after logging in to the MY ACCOUNT.

PLEASE NOTE!

The autoupdate option is relevant only when signalling devices are operated in a network.

 

Cooperating products

USB cable for alarm devices

Use: USB type A – microUSB type B cable designed for alarm devices: SG-Pgw3 SGO-Pgw SGO-Pgz3 SG-Wgw2 SG-Wgw2 IP65 Cable…

wyłącznik akustyczny pożarowego sygnału dźwiękowego

WSD-1 audible signal switch

Use: The WSD-1 audible signal switch is destined for collaboration with: sounders type SA-K5, SA-K6, SA-K7 sounders type SA-P8, sounders…

puszka instalacyjna PIP-1AN

PIP-3AN cable distribution junction box

PIP-3AN CABLE DISTRIBUTION JUNCTION BOX HOLDS DOCUMENTS ISSUED BY CNBOP-PIB: NATIONAL CERTIFICATE OF CONSTANCY OF PERFORMANCE NO. 063-UWB-0194 NATIONAL TECHNICAL…

Choose language